Safety Warnings
Table of Contents
Expand all | Collapse all
Safety Warnings
Review the cautions and warnings pertaining to the PA-500 Series firewalls prior to
installing the hardware.
To avoid personal injury or death for yourself and others and to avoid
damage to your Palo Alto Networks hardware, be sure you understand and prepare for the
following warnings before you install or service the hardware. You will also see warning
messages throughout the hardware reference where potential hazards exist.
All Palo Alto Networks products with laser-based optical
interfaces comply with 21 CFR 1040.10 and 1040.11.
- When installing or servicing a Palo Alto Networks firewall or appliance hardware component that has exposed circuits, ensure that you wear an electrostatic discharge (ESD) strap. Before handling the component, make sure the metal contact on the wrist strap is touching your skin and that the other end of the strap is connected to earth ground.
- Use grounded and shielded Ethernet cables (when applicable) to ensure agency compliance with electromagnetic compliance (EMC) regulations.
- Do not connect a supply voltage that exceeds the input range of the firewall or appliance. For details on the electrical range, refer to electrical specifications in the hardware reference for your firewall or appliance.
-
Caution: Shock hazardDisconnect all power cords (AC or DC) from the power inputs to fully de-energize the hardware.
- Do not connect or disconnect energized DC wires to the power supply.
- The DC system must be earthed at a single (central) location.
- The DC supply source must be located within the same premises as the firewall.
- The DC battery return wiring on the firewall must be connected as an isolated DC (DC-I) return.
- The firewall must be connected either directly to the DC supply system earthing electrode conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected.
- The firewall must be in the same immediate area (such as adjacent cabinets) as any other equipment that has a connection between the earthing conductor of the DC supply circuit and the earthing of the DC system.
- Do not disconnect the firewall in the earthed circuit conductor between the DC source and the point of connection of the earthing electrode conductor.
- Install all firewalls that use DC power in restricted access areas only. A restricted access area is where access is granted only to craft (service) personnel using a special tool, lock and key, or other means of security, and that is controlled by the authority responsible for the location.
- Install the firewall DC ground cable only as described in the power connection procedure for the firewall that you are installing. You must use the American wire gauge (AWG) cable specified and torque all nuts to the torque value specified in the installation procedure for your firewall.
- The firewall permits the connection of the earthed conductor of the DC supply circuit to the earthing conductor at the equipment as described in the installation procedure for your firewall.
- A suitably-rated DC mains disconnect device must be provided as part of the building installation.